Home

Products

What's New

Downloads

Sales Reps

Request Info

 

SEM1100 Isolator Converter

  • High Accuracy 0.05%
  • 3 Port Galvanic Isolation
  • DIN Rail or Surface Mount
  • User Selectable Input and Output
  • AC or DC Powered

DC - DC ISOLATOR / CONVERTER
SEM1100

INTRODUCTION
The SEM1100 is an isolating converter that accepts most common high level process signals (current and voltage), isolates them electrically and physically, and converts them to another process signal.  It is also possible to have voltage and current outputs simultaneously from a single input.

The isolator is available in AC and DC powered versions, both generating loop excitation for input and output loops at the same time.

Zero and span adjustment potentiometers are conveniently situated on the front panel together with a power ON LED.  Configuration (factory set if specified) can easily be changed by means of internal switches and the use of suitable equipment.

INPUT SPECIFICATION @ 68 °F  

.Current .4-20, 0-20 ma Active or Passive (40 ma max.)
.Voltage .0-100 mv, 0-1, 0-5, 0-10V (20 V max.)
  .or 20-100 mv, 0.2-1, 1-5, 2-10 V (20 V max.)
.Selection .Internal Switches
.Impedance .Voltage = >1M ohm
  .Current = <50 ohms
.Protection .Reverse connection / over voltage
.Loop Supply .25V @ 25ma Nominal (available for input transmitter 27 V max.)

OUTPUT

.Current * .4-20, 0-20 ma Active or Passive
.Voltage * .0-1, 0-5, 0-10 Volts**
.0.2-1, 1-5, 2-10 Volts***
.Selection .Internal Switches
.Load .Current 0 to 1K ohm
.Voltage Max. current 5 ma
.Linearity .0.05% Full Range Output
.Stability .100 ppm/°F
.Notes:
.*     Current and voltage outputs are not isolated from each other.
.**   Available simultaneously with 0-20 ma output
.*** Available simultaneously with 4-20 ma output

GENERAL SPECIFICATIONS

.Supply .90-253 VAC 50/60 Hz or 20-35 VDC
.Power Consumption .4 Watts Max.
.Indication .Power on LED
.Response time .<100 ms for 70% of final reading
.Protection .Internal Fuse 500 ma (T)
.Isolation Input/Output .500 VDC (flash tested @ 1 kV)
.Supply .Flash tested @ 3 kV

APPROVALS

.EMC .Emissions .BS EN 50081
.Susceptibility .BS EN 50082
.Electrical Safety .UL 508 / BS EN 61010-1

MECHANICAL

.Mounting .DIN rail or Surface Mount
.Ambient .32-122 ºF, 10-95% RH non-condensing
.Connections .Captive terminal screws
.Cable size .12 AWG solid / 14 AWG Stranded
.Flammability .UL94, V-0, VDE 0304 STEP 11b

CONFIGURED RANGES AVAILABLE

INPUT   OUTPUT
4-20 ma Passive   VOLTAGE CURRENT
4-20 ma Active   0.0-1 VDC 0-20 ma
0-20 ma Passive   0.2-1 VDC 4-20 ma
0-20 ma Active   0.0-5 VDC 0-20 ma
0-100 mv   1-5 VDC 4-20 ma
20-100 mv   0-10 VDC 0-20 ma
0.0-1 VDC   2-10 VDC 4-20 ma
0.2-1 VDC  
0.0-5 VDC  
1-5 VDC   .Default range:
.Input = 4-20 ma
.Output = 4-20 ma or 1-5 VDC
0-10 VDC  
2-10 VDC  

DOWNLOADS
SEM1100 Instruction Manual

SEM1100 Literature


ORDER CODE

SEM1100 / S1 or S2 / ENC1

.SEM1100 Basic Model Number
.Power Options .S1 = 90-253 VAC or
.S2 = 20-35 VDC
.Optional Enclosure .ENCL = NEMA 4 Enclosure holds four SEM1100 units. Size = 5" x 5" x 5"

Call (800) 700-3272 for literature and pricing.  If you prefer to ask for information via the internet use the "REQUEST INFORMATION" button at the top of this screen or e-mail = bm@statinst.com.

 

© 1997 Status Instruments, Inc. - All Rights Reserved