RH and TEMPERATURE TRANSMITTERS

Status Instruments offers In-Transit Hygienic Temperature Data Loggers

To Download Literature Click On The Model Numbers

  Model SEM161
Single Channel
Output
Model SEM162
Dual Channel
Output
    Model SEM165
High Temperature
RH Probe
...RELATIVE HUMIDITY ...RELATIVE HUMIDITY
.RH Range: 0 to 100% RH .RH Range: 0 to 100% RH
Wettable
.Temperature Range: -22 to 212ºF
.Update Time: 3 Seconds .Temperature Range: -22ºF to +284ºF
(-30ºC to 140ºC)
.Start Up Time: 10 Seconds
(I out <4mA during Start Up)
.Response Time:
.(Step Change T90)
<10 seconds
.Accuracy: ±2% .Accuracy: ± 2% RH
.Output: 4 to 20 mA
0 to 100% RH
.Hysteresis: <1%
.Linearity: ± 2.5%
...TEMPERATURE ... (11 to 90% RH)
.Sensor:

Pt100

.Pressure: 400 psi Max.
.Accuracy: ±0.7ºF .Output: 4 to 20 mA
0 to 100% RH
.Output: 4 to 20 mA (-22 to 212ºF)
...OUTPUTS ...TEMPERATURE
.Outputs Available:

Humidity, Temperature, Dew Point
Δ Temperature (Ambient - Dew Point)

.Sensor:

Pt100

.Accuracy:

± 1.8ºF

.Number of Outputs: 1 2 .Output: 4 to 20mA (32 to 212ºF)
.Output Type: 2-Wire Current Loop (4 to 20 mA) ...GENERAL - HEAD ELECTRONICS
.Humidity Range: 0 to 100% RH .Ambient Operating Range:

-4ºF to 131ºF
5 to 95% RH
(non-condensing)

.Temperature Range: -22 to 212ºF
.Dew Point Range: -22 to 212ºF
.Tamb - Tdew point: 32 to 122ºF .Supply Voltage 12 to 32 VDC
.Output Connection: Two Connection Screw Terminal .Load (Vs-12) /20 = K ohms
.Maximum Output: 20.5 mA (in high burnout condition) ...APPROVALS
.Minimum Output: 3.9 mA (in low burnout condition) .Emmissions BS EN 61326
.Accuracy: (mA output / 2000) or 5 µA ...DOWNLOADS
.. (whichever is the greater) .Literature LIT
.Loop Voltage Effect: 0.2 µA / A .Instruction Manual IM
.Thermal Drift: 1 µA / ºC    
.Maximum Output Load: [(Vsupply - 10)/20] K Ohms
(Example: 700 Ohms @ 24V)
   
   
.Channel Isolation: 500 VDC    
...DISPLAY OPTION    
.Type: 4 Digit (9 mm) Red LED    
.Variables Displayed: RH, Dew Point and Temperature    
.Resolution: 0.1% - 0.1 ºF/ºC    
.Update Rate: 800 ms    
...PROBE    
.Ambient Operating Range: -22 to +212ºF    
.Ambient Humidity Range: 0 to 100% RH    
...TRANSMITTER    
.Ambient Operating Range: -22 to +185ºF    
.Ambient StorageTemperature: -58 to +194ºF    
.Ambient Humidity Range: 0 to 90% RH non condensing    
...DOWNLOADS    
.Literature LIT    
.Instruction Manual IM    

 